Power Supply Mains AC option: 94 to 130 V or 187 to 256 V, 48 Hz to 65 Hz, 2 x 10 VA maximum.DC option: 20 to 60 V, 2 x 200 mA maximum, +ve or –ve ground.
Display/Interface Red LED for indication of steam.
Green LED for indication of water.
Amber LED for indication of fault.
Operating Pressure Dependent on manifold or pipework specifications.
Certifications/Approvals FM
Safety IEC 61508 certified to SIL 3
Features
Detect the unwanted presence of water or steam in lines, columns, and condensate pots
SIL 3 certified to IEC 61508 as required by IEC 61511
Commonly used on steam drums, drain pots, or for steam Turbine Water Induction Protection (TWIP)
Electrodes for use up to 1040 °F (560 °C) and 4350 PSI (300 bar)
Patented design, phase detection and triple redundancy for ultimate reliability
Relay outputs in varying options, for status and fault alarms
Configurable steam/water thresholds to adjust for water purity